ASTM C547
Standard Specification forMineral
Fiber Preformed Pipe Insulation
Type I, II, IV, V
Grade A
Maximum Surface Temperature
ASTM C411 Hot Surface Performance In Compliance with ASTM C547
@
1400 °F (760 °C)
ASTM C447 Maximum Surface Performance In Compliance with ASTM C547
@
1400 °F (760 °C)
Dimension Stability
ASTM C356 Linear Shrinkage 0.60%
@
1200 °F (650 °C)
Compressive Strength
ASTM C165 at 10% 1102 psf (52.8kPa)
at 25% 1906 psf (91.3 kPa)
Density
ASTM C303 11.25 lbs/ft
3
180 kg/m
3
Acoustical Performance
ASTM E1222 – Standard Test Method For Laboratory Measurement of the Insertion Loss of Pipe Lagging
Product Jacket
Frequency (Hz)
800 1000 2000 4000 5000
Insertion Loss (db)
12 x 1.5
Aluminum 0 5 8 18 24
Stainless Steel 1 5 14 21 28
PVC 0 2 9 21 28
12 x 2
Aluminum 0 5 10 19 26
Stainless Steel 1 10 16 24 31
PVC 0 1 12 23 30
12 x 2.5
Aluminum 1 7 10 25 30
Stainless Steel 1 11 14 26 33
PVC 0 3 8 25 31
12 x 3
Aluminum 0 3 14 23 30
Stainless Steel 1 6 17 27 33
PVC 0 3 10 26 29
12 x 4
Aluminum 3 14 13 25 31
Stainless Steel 5 14 16 28 34
PVC 0 8 16 26 31